Power input | Supply voltage | -Phase 220V~240V (+/-15%) 3-Phase 380V-460 (+/-15%) | Input frequency | 44….67 Hz | EMC ?lter | Integrated for second environment (industrial area) - option for ?rst environment (residential area) |
|
Motor output | Output voltage | 0………V-input | Output frequency | 0.5………650 Hz | Overload capability | 120% - 60 sec / 15 min |
|
Control-Mode | V/Hz | Linear, Variable torque curve, user programmable curve | PWM frequency | 800…10000Hz (FIXED / RANDOM) |
|
Display | LED 7-segment display | Programmable, to display various inverter and working parameters |
|
Control hardware (I/O) | Digital inputs | 6(8) dig. inputs (PNP/NPN) | Analogue inputs | 2 x 12 BIT analogue inputs 0…10V, 0(4).....20 mA) | Analogue outputs | 2 analogue output, to assign to various functions (0…10V, 0..20 mA) | Digital outputs | 2 digital outputs (free assignement to different functions) | Relais | 1 switchover contact 5 A 230 V (programmable function) | MODBUS | Inverter control, reading and setting of all inverter I/O channels |
|
Specials | Aux. power supply | Auxiliary power supply: 24V / 50 mA – on terminals 10V potentiometer power supply |
|
Protection functions with Foult memory | Electrical protections | Overvoltage, undervoltage Overcurrent, overload, motor overload, short circuit | Thermal protections | Inverter overtemperature, motor-overload I2xt |
|
Optionals and accessories | Display / keypad | Remote display / keypad unit | Brake | Brake resistors for all kind of applications | PC-Link Software | Smart tool for parameter setting, control an diagnosis | Fieldbus | Gateway modules for all commonly used bus technologies | Parameter copy stick | Smart tool for parameter storage and duplication |
|
Environmental and operating conditions | Protection degree | IP20 / IP21 (option) | Operating temperature | -10……+40 °C | Humidity | Max. 90 % non condensing, non corrosive | Altitude | 1000 m, above derating of 1% / 100m |
|